Fire protection in data centers must operate without failure. A minor disruption can cause major operational losses. Therefore, Fire Detection and Alerting System, Fire Alarm Panel requires strict inspection and routine testing.
ODG Nusantara Jaya has successfully completed Fire Detection and Alerting System, Fire Alarm Panel projects in multiple strategic data center facilities. The team follows detailed procedures and industry standards.
Panel Inspection and Control Equipment
The team inspects fire indicator panels, sub-indicator panels, and mimic panels monthly. Each panel must remain visible, accessible, and free from dust. We inspect 100% of installed panels every month.
We also verify control equipment for alarm, supervisory, and trouble signals. All installed panels undergo full monthly inspection.

Supervisory and Waterflow Devices Testing
The team reviews monitoring reliability records for supervisory and waterflow devices. We inspect 100% of waterflow devices quarterly. This schedule ensures all devices are inspected within one year.
Function tests include interfaced equipment, lamps, LEDs, supervisory devices, and waterflow devices. All signalling devices follow a structured annual testing plan.
Battery, Releasing Devices, and Alarm Simulation
We check and test sealed lead-acid batteries in the fire alarm control unit. The team tests 100% of installed batteries.
Electromechanical releasing devices, suppression system switches, and manual fire alarm boxes receive testing every six months. This approach ensures full annual coverage.
We simulate alarm conditions through selected zones or loops. The team confirms visual and audible indicators activate properly. Monitoring providers must receive and process the alarm correctly.
Detector and Notification Appliance Testing
We test 100% of smoke detectors using approved aerosol agents. Heat detectors undergo testing with a calibrated heat source. All detectors are tested within one year.
Fire bells and notification appliances also receive 100% testing to guarantee clear emergency alerts.
Fault Simulation and Fire Loop Testing
The team simulates fault conditions at the fire indicator panel. We confirm trouble signals reach the monitoring provider. Sub panels must indicate alarms at the main fire panel.
Fire loop testing identifies open circuits, ground faults, and short circuits. Every loop must operate accurately.
Fire Intercom System
We conduct visual inspection of fire intercom panels. The team checks supply voltage, power supply, and battery condition. Trouble signals are verified on 100% of installed panels.
Evacuation scenario testing confirms intercom functionality during emergencies. We test 50% of units annually. Battery testing and panel cleaning complete the maintenance cycle.
ODG Nusantara Jaya delivers reliable fire protection solutions that keep data center operations secure and compliant.